{
  "meta": {
    "disclaimer": "Do not rely on openFDA to make decisions regarding medical care. While we make every effort to ensure that data is accurate, you should assume all results are unvalidated. We may limit or otherwise restrict your access to the API in line with our Terms of Service.",
    "terms": "https://open.fda.gov/terms/",
    "license": "https://open.fda.gov/license/",
    "last_updated": "2026-07-08",
    "results": {
      "skip": 0,
      "limit": 1,
      "total": 1
    }
  },
  "results": [
    {
      "status": "Ongoing",
      "city": "Buc",
      "state": "N/A",
      "country": "France",
      "classification": "Class II",
      "openfda": {},
      "product_type": "Devices",
      "event_id": "99042",
      "recalling_firm": "GE Medical Systems SCS",
      "address_1": "283 rue de la Miniere",
      "address_2": "N/A",
      "postal_code": "N/A",
      "voluntary_mandated": "Voluntary: Firm initiated",
      "initial_firm_notification": "Letter",
      "distribution_pattern": "Worldwide distribution - United States Nationwide and the countries of Algeria, Australia, Belarus, Belgium, Benin, Brazil, Bulgaria, Canada, Chile, Colombia, Croatia, Denmark, Finland, France, Germany, Greece, Hungary, India, Indonesia, Iraq, Israel, Italy, Japan, Korea (Republic Of), Lithuania, Morocco, Nepal, Netherlands, New Zealand, North Macedonia, Norway, Pakistan, Poland, Portugal, Romania, Russia, Saudi Arabia, Slovakia, South Africa, Spain, Sweden, Switzerland, Taiwan, Thailand, Tunisia, Turkiye, United Arab Emirates, United Kingdom, Vietnam.",
      "recall_number": "Z-2553-2026",
      "product_description": "GE Healthcare AW Server 3.2 ext.6.5; Radiological Image Processing System",
      "product_quantity": "340 servers",
      "reason_for_recall": "GE HealthCare has become aware of a context synchronization issue in AW Server 3.2 ext. 6.5. When a user selects a patient or exam in the AW Server Web Client worklist and launches an interactive application (e.g. Volume Viewer), the application may open the previous patient's exam instead of the intended one.  When this issue occurs, there is no system warning or error notification. If the error is not recognized, a clinical user could review, interpret, or report images for the wrong patient which could lead to misdiagnosis, incorrect clinical decisions, resulting in delayed or incorrect treatment.",
      "recall_initiation_date": "20260508",
      "center_classification_date": "20260624",
      "report_date": "20260701",
      "code_info": "REF# (01)00840682102384(10)AWS03D02E6D5, GTIN Number 00840682102384"
    }
  ]
}